Published January 10, 2023 | Version v1
Dataset Open

Operation SCADA Dataset of an Urban Small Wind Turbine in São Paulo, Brazil

  • 1. University of São Paulo (USP), Institute of Energy and Environment (IEE), Center for Analysis, Planning and Energy Resources Development (CPLEN)

Description

The dataset file contains data regarding the electrical and mechanical operational actual quantities and parameters obtained and recorded by the internal inverter controller of a Skystream 3.7 small wind turbine (SWT) installed on the roof of the High Voltage Laboratory at the Institute of Energy and Environment (IEE) of the University of Sao Paulo (USP), Brazil, recorded from 2017 to 2022.

The main electrical parameters are the energy, voltages, and currents in the connection grid point and power frequency. Mechanical information can be retrieved, such as the rotation and the wind speed. The temperature, measured in some location points to the nacelle and inverter, is also recorded. Several other parameters concerning the SWT inverter operation, such as the dc voltages on its internal bus, alarms, and flags, are also presented.

The files in the dataset are named as "data_swt_iee_usp_YYYY.csv" where YYYY is the referring year. In the files, the semicolon symbol (;) is used as a column separator, while the dot symbol (.) represents the decimal separator. The first row of the CSV file corresponds to the header row to help identify data as described in the file "data_description.txt". Sampling rate one record per minute.

The first line on each year-based file represents the header table description of the data columns.

The complete and detailed information about the installation, localization,and analysis is in the article published at: https://doi.org/10.3390/wind2040037

LIST OS STATUS CODES - Skystream 3.7

Premise: Binary logic, where each status is represented by a specific bit within an integer value.

Numeric Code Turbine Status Grid Status System Status
0 Normal. Run with energy generation Normal (No faults detected) Normal (System operating without errors)
1 Low Windspeed L1 Low Voltage HS Backoff
2 Braking L1 High Voltage SIP TX Too Long
4 Overspeed L2 Low Voltage Improper Reset
8 No Stall (Normal Operation) L2 High Voltage Battery Timeout
16 High Wind Test Offset Limit Drive Off
32 Anemometer mode Phase Error Slave Shutdown
64 Ramp Frequency Low Temp Shutdown
128 TSR Incr Frequency High High Temp
256 Power High DPLL Unlock Run (Normal Operation)
512 TSR Limit Grid Disconnect Disabled
1024 Quiet Anti-Islanding Waiting
2048 Incr Delay   Temp Backoff
4096 RPM Control   Bad Setpoints
8192 Vin High   Bad CRC

 

These codes can represent cumulative causes, adding values when multiple causes occur.

EXAMPLES:

Turbine status = 0  => Generating/Run

Turbine status = 1 => Low Windspeed

Turbine status = 3 => Low Windspeed and Braking

Turbine status = 9 => Low Windspeed and No Stall

Turbine status = 33 => Anemometer mode and Low Windspeed

System status = 1024 => Waiting

System status = 256 => Run

Grid status = 512 => Grid Disconect

Files

data_description.txt

Files (258.5 MB)

Name Size Download all
md5:d811f7a09890822afc24cfba64ced196
2.9 kB Preview Download
md5:8fbc1a6e3436c1284d88009810f3fbc8
5.3 MB Preview Download
md5:cc718046e3bebb61019928f79dbcfad9
45.1 MB Preview Download
md5:decc2b40fed02763e3707b69e4d0806b
54.7 MB Preview Download
md5:bf0392b948fc14775416196f1a6ca03d
40.5 MB Preview Download
md5:ee83dd4f76326d699276eecd5cd678c5
46.7 MB Preview Download
md5:39031f1dbf357a0613ac642ae8bc24d4
66.3 MB Preview Download

Additional details

Related works

Is source of
Journal article: 10.3390/wind2040037 (DOI)