Published December 1, 2021 | Version v1
Journal article Open

Frequency regulation service of multiple-areas vehicle to grid application in hierarchical control architecture

  • 1. Chiang Mai University

Description

Regarding a potential of electric vehicles, it has been widely discussed that the electric vehicle can be participated in electricity ancillary services. Among the ancillary service products, the system frequency regulation is often considered. However, the participation in this service has to be conformed to the hierarchical frequency control architecture. Therefore, the vehicle to grid (V2G) application in this article is proposed in the term of multiple-areas of operation. The multiple-areas in this article are concerned as parking areas, which the parking areas can be implied as a V2G operator. From that, V2G operator can obtain the control signal from hierarchical control architecture for power sharing purpose. A power sharing concept between areas is fulfilled by a proposed adaptive droop factor based on battery state of charge and available capacity of parking area. A nonlinear multiplier factor is used for the droop adaptation. An available capacity is also applied as a limitation for the V2G operation. The available capacity is analyzed through a stochastic character. As the V2G application has to be cooperated with the hierarchical control functions, i.e. primary control and secondary control, then the effect of V2G on hierarchical control functions is investigated and discussed.