Published April 28, 2018 | Version v1
Journal article Open

Initialization and synchronization of power hardware-in-the-loop simulations: a Great Britain network case study

  • 1. University of Strathclyde

Description

The hardware under test (HUT) in a power hardware in the loop (PHIL) implementation can have a significant effect on overall system stability. In some cases, the system under investigation will actually be unstable unless the HUT is already connected and operating. Accordingly, initialization of the real-time simulation can be difficult, and may lead to abnormal parameters of frequency and voltage. Therefore, a method for initializing the simulation appropriately without the HUT is proposed in this contribution. Once the initialization is accomplished a synchronization process is also proposed. The synchronization process depends on the selected method for initialization and therefore both methods need to be compatible. In this contribution, a recommended practice for the initialization of PHIL simulations for synchronous power systems is presented. Experimental validation of the proposed method of establishing a PHIL simulation for a Great Britain network case study demonstrates the effectiveness of the approach in achieving stable operation. 

Files

Guillo-Sansano-etal-Energies-2018-Initialization-and-synchronization-of-power-hardware-in-the-loop-simulations.pdf

Additional details

Related works

Is previous version of
https://strathprints.strath.ac.uk/63892/ (URL)

Funding

European Commission
ERIGrid – European Research Infrastructure supporting Smart Grid Systems Technology Development, Validation and Roll Out 654113
European Commission
ELECTRA – European Liaison on Electricity Committed Towards long-term Research Activities for Smart Grids. 609687