A Synchronization Scheme for Single-Phase Grid-Tied Inverters under Harmonic Distortion and Grid Disturbances
- 1. KIOS Center of Excellence, University of Cyprus
- 2. Department of Energy Technology, Aalborg University
- 3. KIOS Center of Excellence, and Department of Electrical and Computer Engineering, University of Cyprus
Description
Synchronization is a crucial aspect in grid-tied systems, including single-phase photovoltaic inverters, and it can affect the overall performance of the system. Among prior-art synchronization schemes, the Multi Harmonic Decoupling Cell Phase-Locked Loop (MHDC-PLL) presents a fast response under grid disturbances and high accuracy under harmonic distortions. However, major drawbacks of the MHDC-PLL include increased complexity and inaccurate response under non-nominal frequencies, which may occur in practical applications. Thus, this paper proposes strategies to address these issues. At first, a novel re-formulation of an equivalent decoupling cell is proposed for reducing the implementation complexity, and then a frequency adaptive quadrature signal generator for the MHDC-PLL is proposed to enable an accurate response even under non-nominal frequencies. Simulation and experimental results are provided, which show that the proposed synchronization (i.e., the frequency adaptive MHDC-PLL) can achieve a fast and accurate response under any grid disturbance and/or severe harmonic conditions.
Notes
Files
TPEL - Reg - 2016-01-0141_Final Paper.pdf
Files
(2.0 MB)
Name | Size | Download all |
---|---|---|
md5:fd738e37dd347da0544db0ddc1c4a159
|
2.0 MB | Preview Download |
Additional details
Related works
- Is previous version of
- 10.1109/TPEL.2016.2581019 (DOI)