Info: Zenodo’s user support line is staffed on regular business days between Dec 23 and Jan 5. Response times may be slightly longer than normal.

Published June 1, 2023 | Version v1
Journal article Open

Study of the performance of fault-tolerant multi-level inverter included in shunt active power filter

  • 1. Research Center in Industrial Technologies (CRTI)
  • 2. University of Constantine 1
  • 3. University of Sciences and Technology of Oran Mohamed Boudiaf

Description

Nowadays, the large number of shunt active power filters (SAPF) is installed in many grid networks to eliminate the source currents harmonics and enhance power quality. These filters are installed in different places according to the filtration requirements. The connection between SAPF and grid network has a negative effect during the open-circuit fault of the insulated gate bipolar transistor (IGBT) switch of the SAPF. This paper proposes the application of the new diagnostic method based on the trigonometric circle and mean value variations techniques to the early detection and precise location of the open-circuit fault of the IGBT switches, and the inclusion of the modified reconfigurable inverter topology to allow the perfect continuity of the filter currents, and improve the diagnostic of the open-circuit fault. A single-sided amplitude spectrum technique (SSAS) is applied on the source currents to get the THDi% value. The obtained simulation results prove, the great success of the proposed diagnostic method, the ability of the modified reconfigurable inverter to be adapted to the grid network, the short response time between the diagnosis and the reconfiguration process is about 7 ms which is very sufficient to guarantee the rapid continuity of the shunt active power filter.

Files

v 10 28118 EMr K.pdf

Files (799.7 kB)

Name Size Download all
md5:c6648f641061d453c5ae15fc08c6f257
799.7 kB Preview Download