DIAGNOSTICS OF THE THYRISTOR BRIDGE FAULT BASED ON THE DETECTION OF THE LINE-FREQUENCY SECOND HARMONIC IN THE OUTPUT CURRENT OF AN AC/DC CONVERTER
Creators
- 1. The Nikola Tesla Institute of Electrical Engineering, University of Belgrade
Description
In this paper was presented the technical procedure implemented for the fault diagnostics of the thyristor bridge in an АС/DC converter. During the development of the new generation of digital controllers for AC/DC converters, it was required for these devices to have a possibility for a real-time detection of the thyristor converter fault. Thyristor bridge fault should be detected without the need for the state monitoring of the particular power semiconductor switches or rapid fuses. Thyristor bridge fault was identified using the measurement of the line-frequency second harmonic in the rectifier output current signal. Output voltage and current waveforms were presented, as well as the current spectra, in the cases of the thyristor bridge operation without one switch. The operation principle was described for a protection from an asymmetric operation of a thyristor bridge. A negative influence of high-order harmonics was analysed on the particular rectifier components, both in the cases of the output voltage control, as well as for operation in the current limit mode.
Files
0040-21761801099V.pdf
Files
(458.6 kB)
Name | Size | Download all |
---|---|---|
md5:c029a9d60267ecd56920e6608e683ad7
|
458.6 kB | Preview Download |
Additional details
Funding
- Energy efficiency Improvement of Hydro and Thermal power plants in EPS by development and implementation of power electronics based regulation and automation equipment 33020
- Ministry of Education, Science and Technological Development