A calculation model for determination of impedance of power high voltage single-core cables with polymer insulation
Creators
- 1. National Technical University «Kharkiv Polytechnic Institute», Ukraine
Description
Introduction. The wave parameters of power cables with polymer insulation differ significantly from the parameters of overhead lines and power transformers. As a result, there are more and more objects in electrical networks for which the occurrence of complex multi frequency transients, accompanied by dangerous overvoltages, should be expected. Purpose. To develop a computational model of the complex impedance of high-voltage single-core power cables of coaxial design required to determine the frequency dependencies of the active resistance and inductance of the conductive core and metal shield, taking into account the surface effect and proximity effect. Methodology. The method is based on solving a system of linear algebraic Kirchhoff equations (SLAE) for magnetically coupled contours. SLAE can be used to calculate conductors taking into account the skin effect and proximity effect. Practical value. The developed model is the basis for determining the characteristic impedance of high-voltage single-core power cables in a wide range of frequencies required to establish adequate criteria for evaluating the parameters of high-frequency effects critical for cross linked polyethylene insulation.
Files
A calculation model for determination of impedance of power high voltage single-core cables with polymer insulation.pdf
Files
(446.6 kB)
Name | Size | Download all |
---|---|---|
md5:89a7f14aba56e3d3c032ecbc952aba23
|
446.6 kB | Preview Download |
Additional details
References
- Shidlovsky A.K., Shcherba A.A., Zolotarev V.M., Podoltsev A.D., Kucheryavaya I.N. Kabeli s polimernoi izoliatsiei na sverkhvysokie napriazheniia [EHV cables with polymer insulation]. Кyiv, Institute of Electrodynamics of the NAS of Ukraine Publ., 2013. 552 p. (Rus).
- XLPE-insulated power cables for voltages from 45 kV up to 330 kV. PJSC Yuzhcable Works, Kharkiv. Available at: https://yuzhcable.com.ua/wp-content/uploads/2018/03/Catalogue-XLPE-cables-45-330-kV.pdf (accessed 13 May 2020).
- Bezprozvannych G.V. Zolotaryov V.M., Antonets Y.A. High voltage cable systems with integrated optical fiber for monitoring cable lines. 2020 IEEE KhPI Week on Advanced Technology (KhPIWeek), 2020, pp. 407-410. doi: https://doi.org/10.1109/KhPIWeek51551.2020.9250174.
- Wang H., Cao J., He Z., Yang J., Han Z., Chen G. Research on Overvoltage for XLPE Cable in a Modular Multilevel Converter HVDC Transmission System. IEEE Transactions on Power Delivery, 2016, vol. 31, no. 2, pp. 683-692. doi: https://doi.org/10.1109/TPWRD.2015.2469595.
- Li J., Xu L., Chen X., Zhao A., Liu J., Zhao X., Deng J., Zhang G. Analysis of statistical and frequency characteristics of transient overvoltage of hybrid cable-OHL lines. 2018 China International Conference on Electricity Distribution (CICED), 2018, pp. 2650-2654. doi: https://doi.org/10.1109/CICED.2018.8592463.
- Olsen R.G. Propagation along overhead transmission lines with multiply grounded shield wires. IEEE Transactions on Power Delivery, 2017, vol. 32, no. 2, pp. 789-798. doi: https://doi.org/10.1109/TPWRD.2016.2561977.
- Zhao H., Zhang W., Wang Y. Characteristic Impedance Analysis of Medium-Voltage Underground Cables with Grounded Shields and Armors for Power Line Communication. Electronics, 2019, vol. 8, no. 5, p. 571. doi: https://doi.org/10.3390/electronics8050571.
- Meng J., Wang W., Tang X., Xu X. Zero-sequence voltage trajectory analysis for unbalanced distribution networks on single-line-to-ground fault condition. Electric Power Systems Research, 2018, vol. 161, pp. 17-25. doi: https://doi.org/10.1016/j.epsr.2018.03.024.
- Varetsky Y. Overvoltages in MV industrial grid under ground faults. Energy Engineering and Control Systems, 2019, vol. 5, no. 2, pp. 75-80. doi: https://doi.org/10.23939/jeecs2019.02.075.
- Bezprozvannych A.V., Kessaev A.G., Shcherba M.A. Frequency dependence of dielectric loss tangent on the degree of humidification of polyethylene cable insulation. Technical Electrodynamics, 2016, no. 3, pp. 18-24. (Rus). doi: https://doi.org/10.15407/techned2016.03.018.
- Zhu G., Zhou K., Gong W., He M., Kong J., Li K. Inhibition of rejuvenation liquid on trees in XLPE cables under switching impulse voltages. Energies, 2019, vol. 12, no. 11, p. 2133. doi: https://doi.org/10.3390/en12112133.
- Papazyan R. Concepts for market-based MV cable operations and maintenance using insulation parameters measurements. 2020 12th Electrical Engineering Faculty Conference (BulEF), 2020, pp. 1-5, doi: https://doi.org/10.1109/BulEF51036.2020.9326055.
- IEC 60287-1-1. 2006. Electric cables – Calculation of the current rating - Part 1-1: Current rating equations (100 % load factor) and calculation of losses – General. – 65 p.
- Aloui T., Amar F.B., Abdallah H.H. Fault prelocalization of underground single-phase cables: Modeling and simulation. International Journal of Electrical Power & Energy Systems, 2019, vol. 44, no. 1, pp. 514-519. doi: https://doi.org/10.1016/j.ijepes.2012.07.067.
- Rozov V.Y., Tkachenko O.O., Yerisov A.V., Grinchenko V.S. Analytical calculation of magnetic field of three-phase cable lines with two-point bonded shields. Technical Electrodynamics, 2017, no. 2, pp. 13-18. (Rus). doi: http://doi.org/10.15407/techned2017.02.013.
- Kalantarov P.L., Tseytlin L.A. Raschet induktivnostei [Inductance calculations]. Leningrad, Energoatomizdat Publ., 1986. 487 p. (Rus).