Info: Zenodo’s user support line is staffed on regular business days between Dec 23 and Jan 5. Response times may be slightly longer than normal.

Published March 1, 2021 | Version v1
Journal article Open

Current mode control of single phase grid tie inverter with anti-islandin

  • 1. BMS Institute of Technology
  • 2. Ramaiah University of Applied Sciences

Description

The aim of this paper is to explore the use of various current mode control (CMC) techniques to design a single phase grid tie inverter integrated with anti-islanding protection. Three types of CMC techniques have been discussed, namely current hysteresis control (CHC), constant frequency control (CFC) and average current mode control (ACMC). The performance of the grid tie inverter in the event of grid voltage failure is also studied to help install an anti-islanding mechanism. The proposed control techniques shall eliminate the use of Phase locked loop (PLL) control as the current reference is generated from the grid voltage itself. All three current mode control techniques of an inverter have been simulated in MATLAB/Simulink to evaluate the performance of the designed inverter. The simulated results show a current THD of less than 5% in all three methods and a good anti-islanding response.

Files

24 20868 2021.pdf

Files (403.5 kB)

Name Size Download all
md5:ccfa3658d6992f36cb87dc683beaa320