Description

In this paper, the exergy analysis of vapor absorption
refrigeration system using LiBr-H2O as working fluid is carried out
with the modified Gouy-Stodola approach rather than the classical
Gouy-Stodola equation and effect of varying input parameters is also
studied on the performance of the system. As the modified approach
uses the concept of effective temperature, the mathematical
expressions for effective temperature have been formulated and
calculated for each component of the system. Various constraints and
equations are used to develop program in EES to solve these
equations. The main aim of this analysis is to determine the
performance of the system and the components having major
irreversible loss. Results show that exergy destruction rate is
considerable in absorber and generator followed by evaporator and
condenser. There is an increase in exergy destruction in generator,
absorber and condenser and decrease in the evaporator by the
modified approach as compared to the conventional approach. The
value of exergy determined by the modified Gouy-Stodola equation
deviates maximum i.e. 26% in the generator as compared to the
exergy calculated by the classical Gouy-Stodola method.

Files

10001119.pdf

Files (169.6 kB)

Name Size Download all
md5:39b2a8a51d511f7a313af46c1a52179d
169.6 kB Preview Download

Additional details

References

  • M.A. Hammad, M.S.Audi, Performance of a Solar LiBr-Water Absorption Refrigeration System, Renewable Energy, Vol. 2, 1992, pp. 275-282.
  • S.M. Deng, W.B. Ma, Experimental studies on the characteristics of an absorber using LiBr/H2O solution as working fluid, International Journal of Refrigeration, Vol. 22, 1999, pp. 293–301.
  • Omer Kaynakli, Muhsin Kilic, Theoretical study on the effect of operating conditions on performance of absorption refrigeration system, Energy Conversion and Management, Vol. 48, 2007, pp. 599–607.
  • R.D. Misra, P.K. Sahoob, A. Gupta, Thermoeconomic evaluation and optimization of a double effect H2O/LiBr vapor-absorption refrigeration system, International Journal of Refrigeration, Vol. 28, 2005, pp. 331– 343.
  • S.C. Kaushik, Akhilesh Arora, Energy and exergy analysis of single effect and series flow double effect water–lithium bromide absorption refrigeration systems, International Journal of Refrigeration, Vol. 32, 2009, pp. 1247–1258.
  • Tatiana Morosuk, George Tsatsaronis, A new approach to the exergy analysis of absorption refrigeration machines, Energy, Vol. 33, 2008, pp. 890–907.
  • I. Horuz, T.M.S. Callander, Experimental investigation of vapor absorption refrigeration system, International Journal of Refrigeration, Vol. 27, 2004, pp. 10–16.
  • M.Izquierdo, J.D.Marcos, M.E.Palacios, A.Gonzalez Gil, Experimental evaluation of a low-power direct air-cooled double-effect LiBr-H2O absorption prototype, Energy, Vol. 37, 2012, pp. 737–748.
  • Lampinen, M.J. Wiksten R, Theory of effective heat absorbing and heat emitting temperatures in entropy and exergy analysis with applications to flow systems and combustion process, Journal of Non-equilibrium Thermodynamics, Vol. 31, 2006, pp. 257-291. [10] Holmberg, H., Ruohonen, P. and Ahtila, P, Determination of the real loss of power for a condensing and a backpressure turbine by means of second law analysis, Entropy, Vol. 11, 2009, pp. 702-712. [11] Patek J, Klomfar J, A computationally effective formulation of the Thermodynamic properties of LiBr–H2O solutions from 273 to 500 K over full composition range, International Journal of Refrigeration, Vol. 29, 2006, pp. 566–578.