Monthly production and open-circuit string voltage measurements after 10-year operation of three photovoltaic plants in Southern Spain affected by severe potential-induced degradation
- 1. Department of structural mechanics and hydraulic engineering. University of Granada (UGR)
- 2. University of Granada
Description
Data are formated in a spreadsheet file. Data are presented from three photovoltaic plants in Southern Spain (Córdoba province - Northern Andalucía) designed and installed by the same person, with the same photovoltaic module and the same model of inverter, deployed at the same time (end 2009). The plants are severely affected by potential-induced degradation (PID), so that secondary effects produce some by-pass diodes to activate, producing three families of open-circuit voltage (Voc) in the modules (~40V), (~26V) and (~12V) of a total of nominal Voc of 42,6V.
Monthly production is shown along 11 years (2010-2021), and the measurements of the open-circuit voltage of the strings after 10 years of operation along with the voltage range of the modules of each string.
Sheet 1: configuration of the architecture of the three photovoltaic plants and the features of the photovoltaic module installed.
Sheet 2: energy production for 11 years of opetation. In the last years some recovery is shown in plant 1 and 2 because a repowering project.
Sheet 3: partial climate data of the towns were the plants are located.
Sheet 4: open-circuit voltages of the strings and number of modules in each string with open-circuit voltage in the ranges (~40V) and (<=26V) in plant 1, july-2018.
Sheet 5: open-circuit voltages of the strings and number of modules in each string with open-circuit voltage in the ranges (~40V), (~26V) and (~12V) in plant 2, july-2020.