Robustness of commissioned coordinated Q-V controller for multi-machine power plant
Authors/Creators
- 1. Electrical Engineering Institute "Nikola Tesla", University of Belgrade, Belgrade, Serbia
- 2. University of Manchester, Manchester, UK
Description
This paper presents commissioning details of a coordinated reactive power-voltage controller (CQVC) installed in a multi-machine steam power plant (SPP). The CQVC regulates reactive power and voltage of a 1992MVA multi-machine SPP. After briefly introducing basic control principles and relevant details about the CQVC's implementation, CQVC parameterization and tuning are thoroughly discussed. Once commissioned the CQVC performance under various operating conditions is assessed. It is shown that the CQVC successfully maintains a HV busbar voltage and allocates reactive power to participating generators in accordance to their capability. Numerous CQVC responses recorded at the site are presented to demonstrate controller's performance under normal and extreme plant and network operating conditions.
Files
Robustness of Commissioned Coordinated Q–V Controller for Multi-machine Power Plant.pdf
Files
(837.9 kB)
| Name | Size | Download all |
|---|---|---|
|
md5:020be2c3ca27128acc2177824651a83c
|
837.9 kB | Preview Download |
Additional details
Funding
- Ministry of Education, Science and Technological Development
- Energy efficiency Improvement of Hydro and Thermal power plants in EPS by development and implementation of power electronics based regulation and automation equipment 33020