Operational Reliability of a Gas-Constrained Thermal Fleet: Evidence from Unit-Level Dispatch Reports in Bangladesh

  • 1. Independent Researcher

Description

This paper builds a unit-level reliability dataset for Bangladesh's power fleet from 2,578 public daily reports of the National Load Dispatch Centre (Oct 2019 – Nov 2026): 409,029 unit-days for 225 generating units and 1,587 generator trips. Parsed figures match the reports' printed national totals, and inferred fuels match official generation by fuel within 1%.

For 2019–2024 it reports IEEE 762-style metrics (EFOR, EAF, MTBF/MTTR, Weibull and Crow-AMSAA fits) by technology. Combined-cycle units had an EFOR of 0.13 and an availability of 0.80, falling to 0.71 when fuel shortages are counted. Fuel, not equipment, was the main reason thermal capacity stood idle. Rain raised generator trips, mainly through electrical faults; daily heat did not increase forced outages. Private units tended to spend fewer days in forced outage than state-owned units, but this comparison is suggestive only.

All data are public. Code and generated outputs accompany the paper.