Thermal stratification in an underfloor-ventilated room: code_saturne vs OpenFOAM against the Zhang & Chen (2006) experiment
Authors/Creators
Description
Steady RANS (Boussinesq, standard k-ε) cross-comparison of code_saturne v9.1 and OpenFOAM v2406 (buoyantBoussinesqSimpleFoam) on the same 2,660,663-cell hexa-dominant mesh (snappyHexMesh), reproducing the underfloor air distribution (UFAD) experiment of Zhang & Chen (2006): a 4.91 x 2.44 x 4.31 m occupied room, 4 heated manikins (100 W each) and 6 ceiling lamps (64 W each), two floor-level supply inlets and a ceiling exhaust. Validated against the vertical temperature/velocity profiles published at 7 poles (Fig. 5 of the reference paper): both codes are nearly indistinguishable from each other (MAE on T* of 0.121/0.109, on velocity magnitude of 0.024/0.022 m/s for code_saturne/OpenFOAM), with a shared ~0.6 K cold bias in the occupied zone attributed to the absence of a radiation model. Includes case definitions for both solvers (setup.xml, user-function source, OpenFOAM dictionaries with the codedMixed heat-flux BC), the shared mesh (MED and native OpenFOAM formats, plus the snappyHexMesh generation recipe and logs), full converged-state 3D fields (EnSight Gold for code_saturne, native OpenFOAM for the other), the extracted validation profiles, the digitised experimental reference data, and the post-processing scripts. See README.md for the full modelling table, results table and reproduction instructions.
Files
case_setup__code_saturne__setup.xml
Files
(922.7 MB)
| Name | Size | |
|---|---|---|
|
md5:85d5c776d6cbe0ceaaebdaa1feb90adc
|
272 Bytes | Download |
|
md5:98a84fa7456da4a56a488e3eca66539a
|
41 Bytes | Download |
|
md5:297f3e781ea41049a015596b72db4181
|
14.5 kB | Preview Download |
|
md5:7a773a6d811f979e57e9e07fb0efbf71
|
2.1 kB | Download |
|
md5:216cd58755817e343d7ab96cb8f4b981
|
2.3 kB | Download |
|
md5:64c3de3ef980d5503e1d9efef4d77893
|
6.5 kB | Download |
|
md5:306f9aaea656679cbde3c619ea7917aa
|
2.8 kB | Download |
|
md5:94316a02b711a613b0aeb2fc495d0866
|
2.3 kB | Preview Download |
|
md5:2b96beb1714d4ea2b662b5875579530d
|
847.9 kB | Preview Download |
|
md5:e2b870b4bdbd603fb0ee8847a88d30fb
|
869.9 kB | Preview Download |
|
md5:7e70ef8bdea73fa5d02d638494a1303f
|
330.5 kB | Preview Download |
|
md5:a54e402bda42adf4f4be6835659e006d
|
584.1 kB | Preview Download |
|
md5:794532eb5268cf509d1bd2ff83645efd
|
205.2 kB | Preview Download |
|
md5:799d11f7f17f9627d9451e8c2adfeef7
|
228.4 kB | Preview Download |
|
md5:1e23c9c0c1d81ed7eef4359caa44992e
|
22.4 kB | Download |
|
md5:d28423e7efa7df12c61f32ffc479eb30
|
177.1 MB | Download |
|
md5:844fadbf186f0126bdfe13170aa0660b
|
85.1 MB | Download |
|
md5:a11ee7933b6cf1db4803524598ac2849
|
13.4 kB | Preview Download |
|
md5:24d18039882eb1d424ca6e3afdb3410c
|
410.6 MB | Download |
|
md5:486b4ea8335fa93c0605b930c48a3d09
|
33.5 kB | Download |
|
md5:fb5d89e12ba17f7078ab69ec222eeebf
|
388.4 kB | Download |
|
md5:44ab0da2ac319b18c92c9890fe6ef2c4
|
4.1 kB | Preview Download |
|
md5:0556f3155ba37c5a02bde176f0154954
|
14.3 kB | Preview Download |
|
md5:cd64787f0fdac3b2a447d68e35be029d
|
205.0 kB | Preview Download |
|
md5:7967c89792e252d0cd15f25b657f233b
|
245.9 MB | Download |
|
md5:b7f4dc141334bc741f332221e14bcaa9
|
64.2 kB | Preview Download |
|
md5:47f84a4adaa21c44198e553050dd3dfb
|
64.1 kB | Preview Download |
|
md5:7fe3303d57707ef553e33b0df6924619
|
19.3 kB | Download |
Additional details
Related works
- Is supplement to
- Other: https://simvia.tech/fr/resources/blog/code-saturne-convective-heat-transfer (URL)
- References
- Journal article: 10.1016/j.atmosenv.2006.01.014 (DOI)
- Requires
- Software: https://www.code-saturne.org (URL)
- Software: https://www.openfoam.com (URL)