Three-Phase Power Flow Dataset for the Brazilian ATU10 Distribution Feeder (Araçatuba - São Paulo)
Description
Repository Description
This document describes the columns and data structure of each file used to model the real Brazilian distribution feeder ATU10 from the city of Araçatuba, São Paulo.
The dataset contains the input data required to reproduce the feeder model allowing static power flow simulations.
Support and questions: cristhiangro@gmail.com
Data Files Description
The dataset is organized into several files describing the electrical components of the distribution system, including buses, branches, transformers, switches, generators, and base values.
DATA_BUS.DAD
This file contains the bus data of the distribution network.
ID Area phases ID_Real DESCRICAO Type Z I P Vnom Connection
VLN(a)[pu] Deg(a)[deg] VLN(b)[pu] Deg(b)[deg] VLN(c)[pu] Deg(c)[deg]
Pd(a)[kW] Qd(a)[kVAr] Pd(b)[kW] Qd(b)[kVAr] Pd(c)[kW] Qd(c)[kVAr]
Vmin[pu] Vmax[pu]
Vnom
Nominal voltage of the load model in per-unit.
Type
1 - PQ
2 - PV
ZIP Load Model
The parameters Z, I, and P represent the relative participation of each component in the ZIP load model.
For a constant power load (PQ model):
I = 0
P = 1
Any combination is allowed provided that:
Connection
1 - D (Delta)
Phases
The phases field indicates the phases where the loads are connected.
010 - B
001 - C
110 - AB
011 - BC
101 - AC
111 - ABC
DATA_BRANCH.DAD
This file describes all branch elements of the system, including lines, transformers, shunt elements, voltage regulators, and switches.
ID Area phases bus_from bus_to Type
ampacity(A) ampacity(B) ampacity(C)
raa xaa rba xba rbb xbb rca xca rcb xcb rcc xcc
yaa yba ybb yca ycb ycc
NOTE:
All impedance parameters Zabc must be inserted in Ohms.
NOTE 2:
All shunt admittance values Yshunt must be inserted in µS (microSiemens).
Type
1 - Transformer
2 - Shunt Element
3 - Voltage Regulator
4 - Switch
Phases
010 - B
001 - C
110 - AB
011 - BC
101 - AC
111 - ABC
DATA_TRANSFORMER.DAD
This file contains transformer data.
ID branch_id area_prim area_sec connection
bus_from bus_to Snom[kVA] R[pu] X[pu]
Vprim[kV] Vsec[kV] a b
NOTE:
Voltages must be inserted as line-to-line values.
NOTE 2:
The parameters a and b represent tap deviations from nominal voltage at the primary and secondary sides, respectively.
Transformer Connection Types
1 - Ygr - Y
2 - Ygr - D
3 - Y - Y
4 - Y - Ygr
5 - Y - D
6 - D - Ygr
7 - D - Ygr
8 - D - D
DATA_SWITCH.DAD
Switch status in the network.
DATA_GENERATOR.DAD
Generator data used in the simulations.
ID Bus Vset[pu]
Pga[kW] Qga[kVAr]
Pgb[kW] Qgb[kVAr]
Pgc[kW] Qgc[kVAr]
Pmin[kW] Pmax[kW]
Qmin[kVAr] Qmax[kVAr]
DATA_AREAS.DAD
System base values.
ID Sbase[MVA] Vbase[kV]
NOTE
Vbase must be inserted in kV