On the appropriateness of Fire Dynamics Simulator for the road tunnel smoke control problem
Authors/Creators
- 1. Stacey Agnew Pty Ltd, Darra, Australia
Description
NIST have made publicly available [1], [2], [3] Fire Dynamics Simulator (FDS) simulations of the Memorial Tunnel tests [4], [5]. Those FDS results can be analysed to extract a critical velocity value. That is done here, with comparison to the critical velocities observed and recorded during the Memorial Tunnel tests. The conclusion is that, for the region of interest (HRR above 30 MW), for the Memorial Tunnel cross section without the ceiling, FDS overpredicts critical velocity by 40% or so. The reasons for the overpredictions are not disclosed by the developer, and so it is unclear how the underlying issues will affect tunnel systems different to the Memorial Tunnel. Consequently, from a practitioner’s point of view, FDS is not a reliable tool to accurately assess critical or confinement velocities in road tunnels as long as the underlying problem for the discussed overpredictions are not understood and not demonstrated to be appropriately resolved.
Files
StaceyBeyerFDSnote20250702-preprint.pdf
Additional details
Dates
- Submitted
-
2025-07-01Revision 1