Vertical flame spread with horizontal projection
Description
This report consists of two main parts. The first part focuses on the results from several small
scale experiments. A vertical and combustible wall was exposed to external venting flames
from a lower compartment. A non-combustible horizontal projection was used to reduce the
direct impingement of the venting plume on the wall. The wall consisted of particle board and
the horizontal projection was made of calcium silicate. The effectiveness of the horizontal
projection in preventing vertical fire spread along the wall was studied for six different heat
release rates (33, 37, 42, 47, 51 and 56 kW).
The study investigated how different projection sizes impacted flame height, ignition, vertical
temperature development, and char formation. In this study, 0.075 m and 0.1 m projections
were used principally, while other projections (0.05 m and 0.2 m) were used for specific cases.
The 0.1 m projection was more effective in reducing vertical flame heights and temperature
development compared with the 0.075 m projection. The 0.1 m projection successfully
prevented ignition on wall at 33 kW and 37 kW fires during the 10 min experimental duration,
while the 0.075 m projection prevented ignition at 33 kW fire only. However, at higher heat
release rates, the wall ignited with both projections. Once ignition occurred, flame spread
across the wall surface due to the combined effect of the burner and combustible gases from
the pyrolysis process. The flame spread decreased after char formation on the wall. Char area
and depth increased with higher heat-release rates for both projections, although there were no
significant changes in vertical char height. A longer projection (0.2 m) was more effective by
preventing ignition against 47 kW fire. The longer deflection distance restricted continuous
attachment of flames and heat transfer to the wall.
The second part of this study involves a computational simulation study. A three-storey
building model was constructed using the FDS software ‘PyroSim’, where the flame started at
the bottom compartment. A 3.1 MW fire was simulated and spread to the upper floors through
the window. Two types of projections of variable lengths (0, 0.4, 0.6, and 0.8 m) were placed
over each floor. One projection type was an open-ended ceiling projection, while the other one
was solid wall balustrade (such as balcony with railing). The exterior wall or façade of the
building, along with the projection didn’t include any combustible material. The simulation
study allowed visualization and comparison of the flame trajectory and thermal behaviour of
the ascending plume as it interacted with each projection type. Both projection types of several
lengths (0.4 m, 0.6 m and 0.8 m) effectively reduced thermal impact, by 39% to 91%, on the
upper floors compared with no projection, while the reduction increased with projection
lengths. However, the temperature distribution at upper floor walls was affected by the
projection types and lengths. Additionally, the thermal impact on a nearby building was also
studied in these fire scenarios.