Enhancing the reliance of emergency power supply systems for nuclear facilities using hybrid system
Authors/Creators
- 1. Egyptian Nuclear Power Plant Authority
- 2. Egyptian Atomic Energy Authority
- 3. Al-Azhar University
Description
The performance of an atomic facility depends on the efficient supply of
electricity, particularly emergency loads like monitoring and control
equipment, radiation safety systems, and emergency lights. Most nuclear
facilities rely on diesel generators to supply emergency loads during grid
outages. Due to the diesel generator's imperfections, such as its starting time, it
may fail to deliver power because it is unavailable due to maintenance, failure
to start, or failure to run and supply the load. It cannot immediately supply the
critical loads, resulting in a blackout and the release of radioactive substances
into the environment. To address the previous issues, this paper proposes an
improved method to enhance the reliability of nuclear facilities for providing
electricity to safety and critical consumers during normal and emergency
operating modes. The approach incorporates a photovoltaic (PV)
system/battery, and its robustness and performance are tested using load flow
and transient stability analysis. The simulation results demonstrated the
effectiveness and speed of the proposed method when compared to the
traditional method, as the emergency consumers were successfully powered
within a very short time without fluctuations, and the voltage reduction and
frequency were within the nominal values. The electrical transient analyzer
program (ETAP) is used to validate these results.