Published September 29, 2017 | Version v1

Identification of Multi-Machine Power System Coherent Group in Nigeria

Authors/Creators

  • 1. Oska~Jo & Partners LTD, Edo State, Nigeria.

Description

 This paper discuss Nigeria 330KV integrated power system coherent groups of generators for coherency based analysis method for network reduction to carry out  transient stability analysis for multi-machine power system network. This method is based on the following different indices, the first one is inertia condition index and second one is initial power variation index. The coherency identification method has the ability to identify perfect coherent groups in a very simple way, so that the nature of the machines in the reduced order system is exactly similar to those of the full system. Each coherent group is replaced by a single machine using the method of dynamic equivalent construction. The proposed test system involves the integrated network consisting of 39 buses. 

Files

1142531872.pdf

Files (167.7 kB)

Name Size
md5:7d28092318524f38666991bd0c59389f
167.7 kB Preview Download