Published January 18, 2023 | Version 2

Split Second Analysis Covering High Pressure Gas Flow Dynamics At Pipe Outlet – Mathematical / CFD Investigation

Authors/Creators

  • 1. KEO International Consulting Engineers POB 18108

Description

A detailed investigation covering piped gas flow characteristics in high pressure flow conditions. Such flow analysis can be resolved using established mathematical equations known as the Fanno condition, which usually cover steady state, or final flow conditions. However, in real life, such flow conditions are transient, varying with time. This paper uses CFD analysis providing a split second “snapshot” at what happens at the pipe outlet, and therefore, a closer understanding at what happens at the pipe’s outlet in high pressure gas flow condition.

In this example air was selected for simulation purposes. In HVAC applications, such gas flow conditions can occur in typical applications such as; air compressors releasing high pressure air through a pipe, or compressor over pressure refrigerant gas being released into the atmosphere via a discharge pipe.

Investigation has shown that rather than a steady mass flow rate condition occurring at the pipe outlet, calculated by the Fanno flow condition, a spiked increase in flow rate occurs at the beginning,and then stabilizing after a few seconds, with relatively minor ripples in flow rate. Other observations were also made and commented.

CFD results in mass flow rate were compared with the mathematically derived results, differences were recorded. The CFD analysis showed how the k-omega turbulence model performed well, with the processor stabilizing at an early stage.