Conference paper Open Access

Development of a Wideband Current-to-Voltage Transformer Set for Currents up to 2 kA

Chen, Yeying; Mohns, Enrico; Badura, Henrik; Raether, Peter

This paper describes the setup and characterization of a set of wideband Current-to-Voltage (C-to-V) transformers equipped with symmetrical primary windings. The objective is to use the C-to-V transformer set to calibrate digital instrument transformer (IT) accurately at power frequency and within a wider frequency range to cover power quality aspects. The errors of the 50 A and the 200 A reference current transformer (CT) were within ±10 ppm and μrad at 50 Hz. The frequency responses of the two CTs up to 12 kHz were below 0.1 % and 0.2 crad.

The project 17IND06 Future Grid II has received funding from EMPIR Programme co-financed by the Participating States and from the European Union's Horizon 2020 research and innovation programme
77
53
views
downloads
All versions This version
Views 7777
Downloads 5353
Data volume 21.2 MB21.2 MB