Published February 1, 2019 | Version v1

High Temperature Air Source Heat Pump Coupled with Thermal Energy Storage: Comparative Performances and Retrofit Analysis.

  • 1. Centre for Sustainable Technologies, University of Ulster
  • 2. School of Engineering, Dundalk Institute of Technology

Description

This paper presents the performance analysis and retrofit assessment of a domestic high temperature air source heat pump coupled with thermal energy storage in terms of different system configurations. TRNSYS simulations were used to model the dynamic system, which has been validated against field trial results. The validated models were then simulated with different system configurations under the same boundary conditions to assess its performances. Simulated results showed that continuous coupling between the heat pump and storage to heat the house had the worst performance, while the operation of only the heat pump heating the house obtained the highest efficiency. Although the heat pump cannot compete with the gas boilers in terms of running costs, between 6.6% and 33% of carbon cut can be achieved if the heat pump was retrofitted.

Files

Hewitt_etal2019_comparative performances and retrofit analysis_EnergyProcedia.pdf

Files (843.7 kB)

Additional details

Funding

European Commission
CHESS-SETUP - Combined HEat SyStem by using Solar Energy and heaT pUmPs 680556
European Commission
INPATH-TES - PhD on Innovation Pathways for TES 657466