Published July 8, 2018 | Version v1

Conducted EMI causing Error Readings of Static Electricity Meters

  • 1. VSL B.V., Delft, The Netherlands

Description

Following initial studies showing that conducted electromagnetic interference (EMI) can lead to large error readings of static electricity meters, VSL performed a thorough verification study confirming that wideband currents produced by non-linear, fast-switching loads indeed can lead to significant error readings of static meters. Key parameters of the EMI causing the errors are a short rise time and large peak height of the current step. When dimming linear or non-linear loads such as heaters and energy-saving lamps, the (lack of) internal filter in the dimmer has a large influence on these key parameters.

Notes

The research presented in this paper was funded by the Dutch utility association Netbeheer Nederland.

Files

2018 Rietveld_Conducted EMI causing error readings of static electriciy meters_CPEM2018.pdf

Additional details

Related works

Is identical to
Conference paper: https://ieeexplore.ieee.org/document/8501197 (URL)