Published July 27, 2009
| Version 11691
Journal article
Open
Determination of the Characteristics for Ferroresonance Phenomenon in Electric Power Systems
Authors/Creators
Description
Ferroresonance is an electrical phenomenon in
nonlinear character, which frequently occurs in power system due to
transmission line faults and single or more-phase switching on the
lines as well as usage of the saturable transformers. In this study, the
ferroresonance phenomena are investigated under the modeling of the
West Anatolian Electric Power Network of 380 kV in Turkey. The
ferroresonance event is observed as a result of removing the loads at
the end of the lines. In this sense, two different cases are considered.
At first, the switching is applied at 2nd second and the ferroresonance
affects are observed between 2nd and 4th seconds in the voltage
variations of the phase-R. Hence the ferroresonance and nonferroresonance
parts of the overall data are compared with each
others using the Fourier transform techniques to show the
ferroresonance affects.
Files
11691.pdf
Additional details
References
- G. Kumar, S. Rajan, R. Rangarajan, Analysis of Ferroresonance in a Power Transformer with Multiple Nonlinearities, International Journal of Emerging Electric Power Systems, 2006, Volume:7, Issue:2, Article:2.
- B. Buigues, I. Zamora, V. Valverde, A.J. Mazon, J.I. San Martin, Ferroresonance In Three -Phase Power Distribution Transformers: Sources, Consequences and Prevention, 19th International Conference on Electricity Distribution, CIRED, Vienna 21-24 May., 2007, paper:0197.
- C. Charalambous, Z.D. Wang, J. Li, M. Osborne, P. Jarman, Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kV Circuit, International Conference on Power Systems Transients (IPST-07), Lyon, France, 4-7 June, 2007.
- A. Tokic, V. Madzarevic, I. Uglesic, Numerical Calculations of Three- Phase Transformer Transients, IEEE Transactions On Power Delivery, October 2005, Vol.20, No:4.
- D.A.N. Jacobson, R.W. Menzies, Investigation of Station Service Transformer Ferroresonance in Manitoba Hydro's 230-kV Dorsey Converter Station, Proc. IPST'2001, Intemational Conference on Power Systems Transients, Rio de Janeiro, 2001.
- M.R. Iravani, Chair, Modeling and analysis guide- lines for slow transients- part III: the study of ferroresonance, IEEE Working Group on Modeling and Analysis of Systems Transients, IEEE Transactions on Power Delivery, 2000, 15, 255- 265.
- P.E. Sutherland, R. Manning, Ferroresoance in a 13.8kV Distribution Line, IEEE, 2006, page:2238-2241.
- P. Sakarung, Application of PSCAD/EMTDC and Chaos Theory to Power System Ferroresonance Analysis, International Conference on Power Systems Transients (IPST-05) in Montreal, Canada on June 19- 23, 2005, Paper No. IPST05, 2005, 227
- V.S. Vaseghi, Advanced Signal Processing and Digital Noise Reduction, New York: John Wiley, 1996.