Published March 20, 2008
| Version 5299
Journal article
Open
Investigation of Various PWM Techniques for Shunt Active Filter
Authors/Creators
Description
Pulse width modulation (PWM) techniques have been
the subject of intensive research for different industrial and power
sector applications. A large variety of methods, different in concept
and performance, have been newly developed and described. This
paper analyzes the comparative merits of Sinusoidal Pulse Width
Modulation (SPWM) and Space Vector Pulse Width Modulation
(SVPWM) techniques and the suitability of these techniques in a
Shunt Active Filter (SAF). The objective is to select the scheme that
offers effective utilization of DC bus voltage and also harmonic
reduction at the input side. The effectiveness of the PWM techniques
is tested in the SAF configuration with a non linear load. The
performance of the SAF with the SPWM and (SVPWM) techniques
are compared with respect to the THD in source current. The study
reveals that in the context of closed loop SAF control with the
SVPWM technique there is only a minor improvement in THD. The
utilization of the DC bus with SVPWM is also not significant
compared to that with SPWM because of the non sinusoidal
modulating signal from the controller in SAF configuration.
Files
5299.pdf
Additional details
References
- Joachim Holtz, "Pulse width Modulation-A Survey," IEEE Trans.Industrial Electronics, Vol.39, NO.5, Dec1992, pp-410-420.
- Zhou, K., and Wang, D.: ÔÇÿRelationship between space-vector modulation and three-phase carrier-based PWM: A comprehensive analysis-, IEEE Trans. Ind. Electron., 2002, 49, (1), pp. 186-196.
- Van der Broeck, Skudelny, H.C., and Stanke, G.V.: ÔÇÿAnalysis and realisation of a pulsewidth modulator based on voltage space vectors-, IEEE Trans. Ind. Appl., 1988, 24, (1), pp. 142-150.
- Boys, J.T., and Handley, P.G.: ÔÇÿHarmonic analysis of space vector modulated PWM waveforms-, IEE Proc. Electr. Power Appl., 1990, 137, (4), pp. 197-204.
- J.W. Dixon, J. J. Garcia, and L. Moran, "Control system for three-phase active power filter which simultaneously compensates power factor and unbalanced loads," IEEE Trans. Ind. Electron., vol. 42, no.6, pp. 636- 641, Dec. 1995.
- Subhash Joshi, Aby Joseph and Gautam Poddar, "Active power factor correction for highly fluctuating industrial load" in Proc. Of NPEC- 2003, held at IIT, Bombay.
- Takeshi Furuhashi,shigeru Okuma and Yoshiki Uchikawa. "A Study on the Theory of Instantaneous Reactive Power", IEEE Trans,Industrial Electronics,Vol 37,No1, February 1990,pp-86-90.
- Hyosung Kim and Hirofumi Akagi. "The Instantaneous Power Theory on the Rotating p-q-r Reference Frames" IEEE, International conference, Power Electronics and Drive Systems, July 1999,pp-422-427.
- Vasco Soares , Pedro Verdelho and Gil Marques. "An Instantaneous Active and Reactive Current Component Method for Active Filters."IEEE Trans,vol 15, No 4,July2000 ,pp- 660-669. [10] Ambrish Chandra, Bhim Singh, B. N. Singh and Kamal Al-Haddad. "An Improved Control Algorithm of Shunt Active Filter for Voltage Regulation, Harmonic Elimination, Power-Factor Correction, and Balancing of Nonlinear Loads" IEEE Trans, Power Electronics, Vol. 15, No. 3, May 2000,pp- 495-507. [11] Souvik Chattopadhyay, V.Ramanarayanan "Phase Angle Balance Control for Harmonic Filtering of A Three Phase Shunt Active Filter System" IEEE Proc,APEC,Vol 2,Marc 2002,pp-1087-1093. [12] P. S. Sensarma, K. R. Padiyar, and V.Ramanarayanan "A Comparative Study of Harmonic Filtering Strategies for a Shunt Active Filter"IEEE Proc,Industry application conference,Vol 4,Oct 2000pp-2509-2516.