Electrical Percent Loading Assessment for the Distribution Transformers Residential-Used of a Barangay

  • 1. Instructor, Electronics and Communications Engineering Department, Don Honorio Ventura State University (DHVSU), Philippines
  • 2. Staff Engineer , Technical Services Department , Pampanga I Electric Cooperative (PELCO I), Philippines
  • 3. College Instructor, Electrical Engineering Department, Technological Institute of the Philippines - Quezon City (TIP-QC), Philippines.
  • 4. Production Manager , D'Truck Specialist Inc
  • 5. Dean, College of Engineering of Nueva Ecija University of Science and Technology (NEUST), Philippines.
  • 1. Publisher

Description

Proper rating of transformer is important to maximize the useful life and efficiency of the equipment. A higher or lower rating of the transformer can provide either a higher system loss or disconnection of consumer to an electricity provider. In this study, assessment of residential transformer of a barangay was considered. The percent loading of each transformers was evaluated by the used of the standard set by National Electrification Administration (NEA). The software used in the study is Microsoft Excel 2016 for determining the percent loading of each residential transformers. After the percent loading was identified, clustering of transformers was made according to the loading conditions. Changes in rating were also performed to correct the percent loading of the transformer. From 2017 to 2019, 13 transformers or 48.14 % were underloaded while 6 or 22.22% were found to be overloaded. By changing the rating of the transformer in the barangay, the percent loading of the 6 overload transformers were corrected. For the 13 underloads, 12 of which were amended. Moreover, there is still an underload unit RT19 considering the change in rating the available lowest rating of the transformer was already reached. The researchers recommend using load centering to minimize the number of transformers. To compare the monthly kWhr consumption, the monitor of the daily basis kWHr ingestion using Automated Mapping/Facility Management/ Geographical Information System or AM/FM/GIS was endorsed to identify the peak load of each transformer.

Files

C5920029320.pdf

Files (514.3 kB)

Name Size Download all
md5:3486c4c3e4889cb0568b9908da94d7ab
514.3 kB Preview Download

Additional details

Related works

Is cited by
Journal article: 2249-8958 (ISSN)

Subjects

ISSN
2249-8958
Retrieval Number
C5920029320/2020©BEIESP