<p>This paper describes the setup and characterization of a set of wideband Current-to-Voltage (C-to-V) transformers equipped with symmetrical primary windings. The objective is to use the C-to-V transformer set to calibrate digital instrument transformer (IT) accurately at power frequency and within a wider frequency range to cover power quality aspects. The errors of the 50 A and the 200 A reference current transformer (CT) were within ±10 ppm and μrad at 50 Hz. The frequency responses of the two CTs up to 12 kHz were below 0.1 % and 0.2 crad.</p>