Journal article Open Access

Detection and Localization of Defects in Cable Sheath of Cross-Bonding Configuration by Sheath Currents

Marina Adel


Citation Style Language JSON Export

{
  "publisher": "Zenodo", 
  "DOI": "10.5281/zenodo.3891131", 
  "title": "Detection and Localization of Defects in Cable Sheath of Cross-Bonding Configuration by Sheath Currents", 
  "issued": {
    "date-parts": [
      [
        2020, 
        6, 
        12
      ]
    ]
  }, 
  "abstract": "<p>Nowadays, many researchers are focusing on on-line condition monitoring of high-voltage insulated cable systems to prevent failures.With the aim of reducing the voltage induced in the cable sheaths, cross-bonding (CB) grounding cable systems are used in long distance power transmission land lines.This paper proposes a new criterion for the detection and localization of defects that<br>\nmight occur in the cable sheathwhen aCBconfiguration is adopted. The proposed criterion can be applied at different levels of load current. For the application of the criterion, the cable system under evaluation is modeled using the alternative transient program (ATP) software. Various practical cases were studied, showing the effectiveness of the criterion for the detection and localization of<br>\ndifferent types of defects in simulated cable systems. Furthermore, in order to validate the criteria adopted for the defect detection, based on the ATP model, a real defected case was evaluated. The results obtained proved that this criterion is suitable for the&nbsp; detection and localization of defects in the cable sheaths, when on-line measurements are performed in monitoring applications.</p>", 
  "author": [
    {
      "family": "Marina Adel"
    }
  ], 
  "type": "article-journal", 
  "id": "3891131"
}
18
9
views
downloads
All versions This version
Views 1818
Downloads 99
Data volume 7.8 MB7.8 MB
Unique views 1515
Unique downloads 99

Share

Cite as